CARACTERISTICI
Cooling Capacity HP 22HP
kW 61.5
Btu/h 209800
RT 17.5
Rated current A 29.06
Power input kW 16.62
EER W/W 3.70
Heating Capacity kW 69
Btu/h 235400
RT 19.7
Rated current A 28.40
Power input kW 16.80
COP W/W 4.11
Max. input consumption kW 25
Max. current A 42.1
Capacity adjustment range 50%~130%
Compressor data
DC Inverter compressor Quantity 1
Type Scroll Compressor
Brand HITACHI
Running frequency range Hz 30~390
Rotate speed range rps 10~130
Crankcase heater W 40
Compressor oil Model FV-68H
Original oil volume ml 1100 per compressor
Additional oil volume ml 7000 per compressor
Fan data
Fan motor Type DC
Model DR-310-560-8-1
Quantity 2
Insulation class B
Rated speed rpm 880
Power output W 560*2
Fan blade Material ABS
Type Axial
Drive Direct-driven
Fan Quantity 2
Air flow m3/h 16000
Physical data
Outdoor coil Fin type Hydrophilic Aluminum
Fin thikness mm 0.095
Distance between the fins mm 1.6
Tube outside diameter mm Ø7.94
Tube  type Inner-grooved copper tube
Refrigerant Type R410a
Volume kg 16
Throttle type EXV
Dimension (W*H*D) Net mm 1340*1740*840
Packing mm 1410×1900×910
Weight Net kg 297
Gross kg 315
Outdoor sound level dB(A) 63
Maximum operating pressure MPa 4.5
Piping & wiring data
Pipe size Liquid pipe mm Ø15.88
Gas pipe mm Ø31.8
Max. pipe length Total pipe length m 1000
From OU to farthest IU(Actual length) m 190
From OU to farthest IU(Equivalent length) m 220
From 1st indoor distributor to farthest IU m 40/90
Max. vertical length Between OU & IU(OU above IU) m 90
Between OU & IU(OU below IU) m 110
Between IUs m 30
Between OUs m 0
Connection wire Power wire size mm2 16*4+16(L≤20m)
25*4+16(20m<L≤50m)
Signal wire type 2-core shielded cable
Signal wire size mm2 0.75
Operation temperature range
Cooling Outdoor side °C -5~55
Indoor side °C 16~32
Heating Outdoor side °C -30~30
Indoor side °C 16~32

Notes:

1. Cooling operating temperature range is from -5°C to 55°C (It can be customized down to -10°C). Heating operating temperature range is from -30°C to 30°C.

2. The cooling conditions: indoor side 27°C(80.6°F) DB, 19°C(60°F)WB outdoor side 35°C(95°F) DB.

3. The heating conditions: indoor side 20°C(68°F) DB, 15°C(44.6°F)WB outdoor side 7°C(42.8°F)DB.

4. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

5. The above data may be changed without notice for future improvement on quality and performance.

vrf-615
vrf61
vrf61b
DETALII

COD: THV-E61 KW/ZR1
CAP (KW): 61,5
ZONA: Exterior
PRET (fara TVA): 10943 EURO

CERERE DE OFERTA