CARACTERISTICI
Power supply 220~240V/1N/50Hz
220~240V/1N/60Hz
Operating condition T1 T3
Performance data
Cooling Capacity (T1/T3) HP 3.6
kW 10 9
Btu/h 34100 30690
RT 2.84 2.56
Power input (T1/T3) kW 3.00 3.25
Rated current(T1/T3) A 13.6 16.4
EER (T1/T3) W/W 3.33 2.77
Heating Capacity kW 11
Btu/h 37500
RT 3.13
Power input kW 3.1
Rated current A 14
COP W/W 3.55
Max. input consumption kW 4.4
Max. current A 20
Capacity adjustment range 50%~130%
Compressor data
DC Inverter compressor Quantity 1
Type Twin-rotary Compressor
Brand GMCC
Model ATM240D57UMT
frequency range Hz 10~120
Crankcase heater W 35
Compressor oil Model VG74
Original oil volume ml 670
Fan data
Fan motor Type DC
Brand Trane
Model DRN-310-90-8
Quantity 1
Insulation class B
Protection class IPX4
Power output W 90
Fan blade Material ASG20
Type Axial
Drive Direct-driven
Fan Quantity 1
Air flow m3/h 4000
Physical data
Outdoor coil Fin type Hydrophilic Aluminum
Tube diameter mm Ø9.52
Number of rows 2
Coil length x height x width mm 1003×750×43.3
Tube  type Inner-grooved copper tube
Refrigerant Type R410a
Volume kg 2.6
Throttle type EXV
Dimension (W*H*D) Net mm 1032x810x445
Packing mm 1075×875×495
Weight Net kg 60
Gross kg 65
Outdoor sound level dB(A) ≤56
Maximum operating pressure MPa 4.5
Piping & wiring data
Pipe size Liquid pipe mm Ø9.52
Gas pipe mm Ø15.88
Max. pipe length Total pipe length m 100
From OU to farthest IU m 70
From 1st indoor distributor to farthest IU m 20
Max. vertical length Between OU & IU(OU above IU) m 30
Between OU & IU(OU below IU) m 20
Between IUs m 8
Connection wire Power wire size mm2 3×4.0
Signal wire type 3-core shielded cable
Signal wire size mm2 1.0
Operation temperature range
Cooling Outdoor side °C -5~55
Indoor side °C 16~32
Heating Outdoor side °C -15~30
Indoor side °C 16~32

Notes:
1. Cooling operating temperature range is from -5°C to 55°C. Heating operating temperature range is from -15°C to 30°C.
2. The cooling conditions: indoor side 27°C(80.6°F) DB, 19°C(60°F)WB outdoor side 35°C(95°F) DB.
3. The heating conditions: indoor side 20°C(68°F) DB, 15°C(44.6°F)WB outdoor side 7°C(42.8°F)DB.
4. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
5. The company reserves the right to revise product technical parameter without having to notify the clients individually.

https://vrf-geotermal.ro/wp-content/uploads/2020/05/vrf335.jpg
DETALII

COD: THV-DH 10 KW
CAP (KW): 10
ZONA: Exterior
PRET (fara TVA): 1776 EURO

CERERE DE OFERTA